Solis Three Phase US Inverters 30K-US-SW – 30000 Watt

Solis

25-40K three phase series string inverter are suitable for the installation of three-phase input pv system of commercial and industrial PV plants. WhoseTHDi ˂3, low harmonic distortion against grid. Adopt anti-resonance, single transformer can connect 6M+ in parallel. Perfect commercial site monitoring solution.

Rp 73.000.000

DC Values
Max. power per MPPT: 13.500 W
Max. DC input power: 45.000 W
Max. voltage: 1000 V
Rated voltage: 700 V
Startup voltage: 350 V
Full power MPPT voltage range: 417 V – 800 V
Operating MPPT voltage range: 200 V – 800 V
Max. usable input current per MPPT (amps): 18*4
Max. short circuit input current (amps): 28.1*4
Number of MPPTs/inputs per MPPT: 4/2

AC Values
Nominal output power: 30000 W
Max. apparent output power: 30000 VA
Max. continuous output power: 30000 W
Operating voltage range: 422.4 V – 528 V
Nominal grid frequency: 60 Hz
Operating frequency range: 59.5 Hz – 60.5 Hz
Operating phase: Three Phase
Max. output current (amps): 36.1
Max. overcurrent protection device (amps): 50
Max output fault current and duration: 50,200 ms
Power factor: 0.8 leading … 0.8 lagging
Grid current THD: <3%
DC injection current (mAmps): <50

Efficiency
Peak efficiency: 98.6%
CEC weighted efficiency: 98.3%
MPPT efficiency: >99.5%

Protection
Ground fault monitoring
Islanding protection
Integrated AFCI (DC arc-fault circuit protection)
Integrated DC switch
Rapid shutdown

General Data
Connections: 4 knockout for 1.5″ conduit at bottom and side. DC side Fuse terminal, AC side terminal block
Surge protection: DC class II and AC class III (optional)
Dimensions (W*H*D): 21.1*38.0*14.1 in (535*966*358 mm)
Weight (inverter)/weight (wiring box): 127lbs (57.7kgs)/22.8lbs (10.2kgs)
Topology: Transformerless
Internal consumption: <1W (night)
Ambient operating temperature range: -13 °F to 140 °F (-25°C to 60°C)
Storage environment: -13 °F to 176 °F (-25°C to 80°C)
Enclosure type: NEMA 4X
Noise emission (typical): <30dB(A)
Cooling concept: Natural convection
Max.operating altitude without derating: 13.120 ft (4.000 m)
Compliance: UL 1741, UL 1741 SA, Rule 21 Phase I and II compliant (ready for Phase III), UL 1998, UL 1699B, IEEE 1547, FCC Part 15 (Class A & B), CAN/CSA C22.2 107.1-1

Features
Communication protocol: Modbus RTU (Sunspec compliant)
Communication: Modbus with optional cellular and Wi-Fi
Display: 7.0″LCD color screen display

Data Teknis dan Brosur

 

Kategori: ,

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Solis Three Phase US Inverters 30K-US-SW – 30000 Watt”